| Customization: | Available |
|---|---|
| Type: | Self-Starting Diesel Generator |
| Installation Method: | Portable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1500kw genset 1875kva diesel generator
|
Technical data |
|
|
Genset Model |
SA-1500GF |
|
Prime Power |
1500KW/1875KVA |
|
Rated Voltage |
400/230V |
|
Frequency |
50/60Hz |
|
Power Factor |
0.8(lagging) |
|
The regulating rate of steady voltage |
≤±0.5% |
|
The regulating rate of instantaneous voltage |
≤-15%/ +20% |
|
The time of steady voltage |
≤1.5sec |
|
The waving rate of voltage |
≤1.0% |
|
The regulating rate of steady frequency |
≤3% |
|
The regulating rate of instantaneous frequency |
≤±10% |
|
The time of steady frequency |
3sec |
|
Dimension (L×W×H) (mm) |
6150*2150*2400 |
|
Genset weight (kg) |
14000 |
|
Diesel Engine |
|
|
Brand |
MTU |
|
Model |
12V4000G63 |
|
Number of Cylinders |
12 |
|
Rotating Speed |
1500RPM |
|
Cycle |
Four stroke |
|
Type |
waste gas turbine boost,direct spurting type |
|
Bore×Stroke(mm) |
170*210 |
|
Displacement(L) |
57.2L |
|
Lubricating Capacity(L) |
260 |
|
Speed Governor |
Electrical |
|
Cooling System |
Water-cooled |
|
Speed Stability (%) |
≤5% |
|
Fuel Consumption at 100% Load |
193g/kw.h |
|
Starting Method |
DC24V Electrical starting |
|
Alternator |
|
|
Brand |
Stanmford |
|
Model |
PI 734E |
|
Number of Phase |
3 |
|
Connecting Type |
Three Phase and Four Lines |
|
Number of Bearing |
1 |
|
Grading Protection |
IP23 |
|
Altitude |
≤1000m |
|
Exciter Type |
Brushless (AVR automatic voltage regulating) |
|
Insulation Class |
H degree |
|
The components of the genset |
|
|
(1) MTU Diesel Engine; (2)stanmford Alternator; (3) Control Panel |
|
|
Control Panel |
|
|
The control panel is Quadruplication protection control panel, with the display of frequency table/water temperature/schedule/battery voltmeter. The genset with low oil pressure, high water temperature, over speed emergency, stop and other pre-protection. |
|

Partners
Packing & Delivery
1) Wrap the generator set by stretch film, and put some drying agent.